Adjustment of condensing temperature of the vapor-compression heat pump based on a reciprocating long-stroke compressor stage at fixed temperatures of receiving coolant
The theoretical cycle of a heat pump is considered, which is implemented, among other things, on the basis of a reciprocating long-stroke low-speed compressor stage at fixed temperatures of the receiving coolant. The energy components are the indicated power of the compressor, the heating capacity...
Saved in:
Main Authors: | , , |
---|---|
Format: | Article |
Language: | English |
Published: |
Omsk State Technical University, Federal State Autonomous Educational Institution of Higher Education
2023-06-01
|
Series: | Омский научный вестник: Серия "Авиационно-ракетное и энергетическое машиностроение" |
Subjects: | |
Online Access: | https://www.omgtu.ru/general_information/media_omgtu/journal_of_omsk_research_journal/files/arhiv/2023/%D0%A2.7,%20%E2%84%962%20(%D0%90%D0%A0%D0%B8%D0%AD%D0%9C)/27-35%20%D0%AE%D1%88%D0%B0%20%D0%92.%20%D0%9B.,%20%D0%93%D1%80%D0%BE%D0%BC%D0%BE%D0%B2%20%D0%90.%20%D0%AE.,%20%D0%A3%D1%88%D0%B0%D0%BA%D0%BE%D0%B2%20%D0%9F.%20%D0%92..pdf |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | The theoretical cycle of a heat pump is considered, which is implemented, among other things, on the
basis of a reciprocating long-stroke low-speed compressor stage at fixed temperatures of the receiving
coolant. The energy components are the indicated power of the compressor, the heating capacity of
the consumer, the additional heating capacity supplied to the working fluid of the heat pump before
the compression process, as well as the additional heating capacity supplied to the working fluid of the
heat pump or removed from it during the compression process. As independent control parameters, the
following are considered: the ratio of the mass flow rates of the working fluid of the heat pump and
the receiving coolant; overheating of the working fluid of the heat pump at suction and compression
polytropic index.
The analysis of possible design and non-design modes of operation of the heat pump with fixed
operating parameters of the consumer is carried out. A technique has been developed for determining
the thermodynamic efficiency of an ideal heat pump with various methods of adjustment of the
condensing temperature. The relationship between the conversion factor of a heat pump and various
methods of adjustment of the condensation temperature when using water vapor as its working fluid has
been studied. The presented results of the theoretical analysis reflect the nature of the dependence of
the heating capacity and the conversion factor of the heat pump on the ratio of the mass flow rates of
the receiving coolant and the working fluid of the heat pump, the polytropic index of the compression
process, and superheating of the suction steam. |
---|---|
ISSN: | 2588-0373 2587-764X |