A Fast Fault Detection Scheme for Power Converters In Distributed Generation Systems

In this paper, a fault detection algorithm based on voltage disturbances is proposed and analyzed. This method observes the voltage characteristics instead of the current amplitude, that is the most common approach in power distribution electrical systems. The proposed system uses a dual quadrature...

Full description

Saved in:
Bibliographic Details
Main Authors: Gustavo M. S. Azevedo, Marcelo C. Cavalcanti, Francisco A. S. Neves, Fabricio Bradaschia
Format: Article
Language:English
Published: Associação Brasileira de Eletrônica de Potência 2012-05-01
Series:Eletrônica de Potência
Subjects:
Online Access:https://journal.sobraep.org.br/index.php/rep/article/view/536
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:In this paper, a fault detection algorithm based on voltage disturbances is proposed and analyzed. This method observes the voltage characteristics instead of the current amplitude, that is the most common approach in power distribution electrical systems. The proposed system uses a dual quadrature signal generator for each voltage component in a stationary reference frame to extract its positive- and negative-sequence components. Furthermore, a frequency-locked loop is used to estimate the voltage frequency. The voltage amplitude and frequency instantaneous values are compared with the nominal counterparts by means of hysteresis comparators. As a result, a fast and reliable fault detector system is obtained. Simulations and experimental results are presented to illustrate the feasibility and performance of the proposed scheme.
ISSN:1414-8862