Analysis of Capacitor Unbalance Protection activation due to AC filter tripping incident at ±660kV HVDC Lahore converter station
This study examines an AC filter tripping incident that occurred at Lahore Converter station of ±660kV high voltage direct current (HVDC) Pak Matiari-Lahore transmission project which seriously affected the stable operation of the converter station. The fault current exceeded the trip threshold and...