Refrigerant Selection for Cascade Water-to-water Heat Pump

Based on China National Standard-Number Designation and Safety Classification of Refrigerants, refrigerant for the cascade water-to-water heat pump were selected according to principles of environmental-friendly, safety and thermodynamic cycle performances. Different refrigerant combinations for hig...

Full description

Saved in:
Bibliographic Details
Main Authors: Zhao Haibo, Yang Zhao
Format: Article
Language:zho
Published: Journal of Refrigeration Magazines Agency Co., Ltd. 2012-01-01
Series:Zhileng xuebao
Subjects:
Online Access:http://www.zhilengxuebao.com/thesisDetails#10.3969/j.issn.0253-4339.2012.05.032
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Based on China National Standard-Number Designation and Safety Classification of Refrigerants, refrigerant for the cascade water-to-water heat pump were selected according to principles of environmental-friendly, safety and thermodynamic cycle performances. Different refrigerant combinations for high- and low-temperature cycles in the cascade heat pump were calculated and compared. Results show that combinations of R245fa/R134a, R245fa/R420A, R245fa/R413A, R245ca/R420A are better for the cascade heat pump. It also shows that, considering easy access and economy of refrigerants, R245fa/R134a combination will be a better choice.