A hybrid IDM using wavelet transform for a synchronous generator-based RES with zero non-detection zone
Increased use of renewable energy sources in distribution grids has led to the growing concern over unintentional islanding. Among the available islanding detection methods, the passive methods have larger non-detection zones and are susceptible to system faults. However, they have no effect on powe...
Saved in:
Main Authors: | , |
---|---|
Format: | Article |
Language: | English |
Published: |
AIMS Press
2024-03-01
|
Series: | AIMS Electronics and Electrical Engineering |
Subjects: | |
Online Access: | https://www.aimspress.com/article/doi/10.3934/electreng.2024006 |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
_version_ | 1832590315802853376 |
---|---|
author | Mamun Mishra Bibhuti Bhusan Pati |
author_facet | Mamun Mishra Bibhuti Bhusan Pati |
author_sort | Mamun Mishra |
collection | DOAJ |
description | Increased use of renewable energy sources in distribution grids has led to the growing concern over unintentional islanding. Among the available islanding detection methods, the passive methods have larger non-detection zones and are susceptible to system faults. However, they have no effect on power quality like active methods. We present a hybrid method for the islanding detection of synchronous generator-based renewable energy sources. Here, the larger non-detection zone issue of the passive islanding detection method was reduced by combining it with a wavelet transform. The rate of change of a voltage unbalanced factor was computed from the sequence components of the renewable energy source terminal voltage. Then, the factor was analyzed using a wavelet transform, and a threshold for the factor was found. The robustness of the method was tested for several islanding as well as non-islanding situations. The efficacy of the method was also tested in multi-source test systems. From the analysis, it was observed that the proposed method was fast, reliable, and had a zero non-detection zone. |
format | Article |
id | doaj-art-31288a4b9e574e858b391766cb00130d |
institution | Kabale University |
issn | 2578-1588 |
language | English |
publishDate | 2024-03-01 |
publisher | AIMS Press |
record_format | Article |
series | AIMS Electronics and Electrical Engineering |
spelling | doaj-art-31288a4b9e574e858b391766cb00130d2025-01-24T01:10:21ZengAIMS PressAIMS Electronics and Electrical Engineering2578-15882024-03-018114616410.3934/electreng.2024006A hybrid IDM using wavelet transform for a synchronous generator-based RES with zero non-detection zoneMamun Mishra0Bibhuti Bhusan Pati1Department of Electrical Engineering, Veer Surendra Sai University of Technology, Burla, IndiaDepartment of Electrical Engineering, Veer Surendra Sai University of Technology, Burla, IndiaIncreased use of renewable energy sources in distribution grids has led to the growing concern over unintentional islanding. Among the available islanding detection methods, the passive methods have larger non-detection zones and are susceptible to system faults. However, they have no effect on power quality like active methods. We present a hybrid method for the islanding detection of synchronous generator-based renewable energy sources. Here, the larger non-detection zone issue of the passive islanding detection method was reduced by combining it with a wavelet transform. The rate of change of a voltage unbalanced factor was computed from the sequence components of the renewable energy source terminal voltage. Then, the factor was analyzed using a wavelet transform, and a threshold for the factor was found. The robustness of the method was tested for several islanding as well as non-islanding situations. The efficacy of the method was also tested in multi-source test systems. From the analysis, it was observed that the proposed method was fast, reliable, and had a zero non-detection zone.https://www.aimspress.com/article/doi/10.3934/electreng.2024006microgridrenewable energy sourceislanding detection methodnon-detection zonewavelet transformvoltage unbalance |
spellingShingle | Mamun Mishra Bibhuti Bhusan Pati A hybrid IDM using wavelet transform for a synchronous generator-based RES with zero non-detection zone AIMS Electronics and Electrical Engineering microgrid renewable energy source islanding detection method non-detection zone wavelet transform voltage unbalance |
title | A hybrid IDM using wavelet transform for a synchronous generator-based RES with zero non-detection zone |
title_full | A hybrid IDM using wavelet transform for a synchronous generator-based RES with zero non-detection zone |
title_fullStr | A hybrid IDM using wavelet transform for a synchronous generator-based RES with zero non-detection zone |
title_full_unstemmed | A hybrid IDM using wavelet transform for a synchronous generator-based RES with zero non-detection zone |
title_short | A hybrid IDM using wavelet transform for a synchronous generator-based RES with zero non-detection zone |
title_sort | hybrid idm using wavelet transform for a synchronous generator based res with zero non detection zone |
topic | microgrid renewable energy source islanding detection method non-detection zone wavelet transform voltage unbalance |
url | https://www.aimspress.com/article/doi/10.3934/electreng.2024006 |
work_keys_str_mv | AT mamunmishra ahybrididmusingwavelettransformforasynchronousgeneratorbasedreswithzeronondetectionzone AT bibhutibhusanpati ahybrididmusingwavelettransformforasynchronousgeneratorbasedreswithzeronondetectionzone AT mamunmishra hybrididmusingwavelettransformforasynchronousgeneratorbasedreswithzeronondetectionzone AT bibhutibhusanpati hybrididmusingwavelettransformforasynchronousgeneratorbasedreswithzeronondetectionzone |